15kV Three Conductor 133% Insulation Level Continuous Corrugated Weld

15kV Three Conductor 133% Insulation Level Continuous Corrugated Weld

Armored Cable 15kV Three Conductor 133% Insulation Level Continuous Corrugated Weld

15kV Three Conductor 133% Insulation Level Continuous Corrugated Weld

7Y-0203, 7Y-1013, 7Y-2023, 7Y-4043, 7Y-3503, 7Y-5003, 7Y-7503

Somos Especialistas en Cables. Distribuimos en toda la Republica Mexicana: Innovative Trade Center, Tel: (664) 621 33 36 / 621 30 09 ventas@innovative.com.mx, soporte@innovative.com.mx, Tijuana, B. C. www.innovative.com.mx

Armored Cable 15kV Three Conductor 133% Insulation Level Continuous Corrugated Weld

blindado
aislamiento de EPR
PRESUPUESTO
1. CONDUCTOR: Clase B Trenzado, desnudo, cobre recocido por ASTM B3 y B8, escudo hebra es un material semiconductor extruido
2. AISLAMIENTO: Caucho de etileno propileno (EPR) por ICEA S-93-639 (NEMA WC74)
3. SHIELD: Un blindaje de aislamiento semiconductor extruido y luego una cinta de cobre de 5 milésimas de pulgada sin recubrimiento con un 25% de superposición se aplica de forma helicoidal sobre la capa semiconductora
4. MONTAJE: Los conductores trifásicos están cableados con un alambre y rellenos de tierra de clase B hebra para hacer todo el año, se aplica en general una cinta con aglutinante
5. Armadura: Un, ondulado vaina de aleación de aluminio de la costura de soldadura continua impermeable de acuerdo con UL 1569, la armadura es una prueba de presión y se encuentra con la tierra
requisitos de NEC artículo 250
6. CHAQUETA EN GENERAL: rojo, la luz solar resistente al cloruro de polivinilo (PVC)
7. NORMAS: cable deben ser ensayados de acuerdo con UL 1072 requerimientos para el tipo MV-105, UL 2205 para tipo MC-HL y ICEA S-93-639 (NEMA WC74). Cables cumplen la
UL 1685 y IEEE 1202 / T4L 70.000 Btu / hr y el ICEA T-29-520 210.000 BTU / hr pruebas bandeja de llama vertical y están marcados «para uso CT». Cable cumple AEIC CS-8 calificación
requisitos de prueba
8. AMPACIDAD: Basado en un cable de tres conductores aislados en el aire con una temperatura del conductor de 90 ° C y una temperatura ambiente de 40 ° C por NEC 310.71
9. Temperatura: 90 ° C
10.VOLTAGE: 15 kV
APLICACIONES
energía primaria y la iluminación de los circuitos en las plantas de fabricación y procesamiento, alimentadores en sistemas de distribución industrial y comercial, fuente de alimentación de los auxiliares de estaciones en
centrales eléctricas y subestaciones. Puede utilizarse en lugares húmedos o secos instalados en bandeja abierta, canal o escalera.

Armored Cable 15kV Three Conductor 133% Insulation Level Continuous Corrugated Weld

Shielded
EPR insulation
SPECIFICATIONS OF
1. CONDUCTOR: Class B stranded, bare, annealed copper per ASTM B3 and B8, strand shield is an extruded semiconducting material
2. INSULATION: Ethylene Propylene Rubber (EPR) per ICEA S-93-639 (NEMA WC74)
3. SHIELD: An extruded semiconducting insulation shield and then an uncoated 5-mil copper tape with 25% overlap is helically applied over the semiconducting layer
4. ASSEMBLY: The three-phase conductors are cabled with a Class B stranded ground wire and fillers to make round, a binder tape is applied overall
5. ARMOR: An impervious, corrugated continuous seam-welded aluminum alloy sheath in accordance with UL 1569, armor is pressure-tested and meets the grounding
requirements of NEC Article 250
6. OVERALL JACKET: Red, sunlight-resistant Polyvinyl Chloride (PVC)
7. STANDARDS: Cable shall be tested in accordance with UL 1072 requirements for Type MV-105, UL 2205 for Type MC-HL and ICEA S-93-639 (NEMA WC74). Cables meet the
UL 1685 and IEEE 1202/FT4 70,000 Btu/hr and the ICEA T-29-520 210,000 Btu/hr vertical tray flame tests and are marked «for CT use». Cable meets AEIC CS-8 qualification
testing requirements
8. AMPACITY: Based on a three-conductor cable isolated in air with a conductor temperature of 90°C and an ambient temperature of 40°C per NEC 310.71
9. TEMPERATURE: 90°C
10.VOLTAGE: 15 kV
APPLICATIONS
Primary power and lighting circuits in manufacturing and processing plants, feeders in industrial and commercial distribution systems, power supply to station auxiliaries in
electric power stations and substations. May be used in wet or dry locations installed in open tray, trough or ladder.

7Y-0203, 7Y-1013, 7Y-2023, 7Y-4043, 7Y-3503, 7Y-5003, 7Y-7503

Armored Cable 15kV Three Conductor 133% Insulation Level Continuous Corrugated Weld en: Tijuana, Rosarito, Mexicali, Ensenada, Tecate, San Luis Rio Colorado, Son, La Paz, BCS, Los Cabos BCS, Mexico

Etiquetado con: , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , ,
Publicado en: Cable y Alambre, Wire and Cable

Deja una respuesta

Tu dirección de correo electrónico no será publicada. Los campos obligatorios están marcados con *

*

Descarga Aquí este Catálogo
Caddy Erico Mexico, Caddy Nvent Mexico, Erico Mexico, Nvent Mexico,
Subscribase a este sitio