600V 10 AWG Multiconductor

600V 10 AWG Multiconductor

Armored Cable 600V 10 AWG Multiconductor

600V 10 AWG Multiconductor

7TF-1002, 7TF-1003, 7TF-1004, 7TF-1005, 7TF-1006, 7TF-1007, 7TF-1008, 7TF-1009, 7TF-1010, 7TF-1011, 7TF-1012, 7TF-1013, 7TF-1014, 7TF-1015, 7TF-1016, 7TF-1017, 7TF-1018, 7TF-1019, 7TF-1020, 7TF-1025, 7TF-1030, 7TF-1040, 7TF-1050

Somos Especialistas en Cables. Distribuimos en toda la Republica Mexicana: Innovative Trade Center, Tel: (664) 621 33 36 / 621 30 09 ventas@innovative.com.mx, soporte@innovative.com.mx, Tijuana, B. C. www.innovative.com.mx

Armored Cable 600V 10 AWG Multiconductor

aislamiento XLP
Las fundas de PVC interior y exterior
acero galvanizado o aluminio armadura entrelazada
ESPECIFICACIONES DE
1. CONDUCTOR: Clase B Trenzado, desnudo de cobre, suave
Polietileno reticulado (XLP) tal como fue aprobado por la CSA sobre Tipos RW90 XLP -40 ° C por CSA C22.2,: 2. AISLAMIENTO
N ° 131, código de color: 2 / C negro, blanco; 3 / C rojo, negro, azul; 4 / C rojo, negro, azul, blanco; más de 4 / C numerada
3. Conductor de Tierra: 14 AWG sin aislar Clase B conductor de tierra trenzado está incluido en el conjunto de cables
4. MONTAJE: cables conductores múltiples están montados con cargas adecuadas y cinta con aglutinante
5. chaqueta interior: cloruro de polivinilo (PVC) al calor, a las llamas y una chaqueta resistente a la humedad, una clasificación de -40 ° C
6. Armadura: aluminio o acero galvanizado armadura de enclavamiento
7. CHAQUETA EN GENERAL: El cloruro de polivinilo (PVC) al calor, a las llamas y una chaqueta resistente a la humedad, nominal -40 ° C, el color estándar es negro, pero las chaquetas de colores están disponibles bajo petición,
cumple Ontario Hydro Espec. L-891 SM-77 prueba de la llama y el ensayo de llama vertical de la bandeja FT4
8. AMPACIDAD: Basado en 90 ° C la columna de la Tabla 2 del Código Eléctrico Canadiense de 2009, ampacidades permisibles para no más de 3 conductores de cobre en la pista de rodadura o el cable sobre la base de
30 ° C de temperatura ambiente. factores de corrección de corriente admisible para el número de conductores de la Tabla 5C de la CCA
9. Temperatura: -40 ° C a 90 ° C
10.VOLTAGE: 600 V
APLICACIONES
Para expuesta u oculta el cableado en lugares húmedos o secos. Para su uso en ventilado de transporte por cable flexible, no ventilado y canales de cable tipo escalera y ventilado en húmedo o en seco
ubicaciones. Para el entierro directo. Las aplicaciones típicas son las instalaciones de fuerza, iluminación y control en: fábricas de papel, fábricas de acero, plantas de procesamiento de alimentos, comerciales
centros, minas, estaciones generadoras, refinerías, plantas industriales y plantas químicas.

Nota: Después de su uso el número de catálogo; «SJ» de acero «AJ» de aluminio (por ejemplo 7TF-1003AJ).
Diámetros y pesos pueden variar entre los fabricantes

Armored Cable 600V 10 AWG Multiconductor

XLP insulation
Inner and outer PVC jackets
Galvanized steel or aluminum interlocked armor
SPECIFICATIONS OF
1. CONDUCTOR: Class B stranded, bare, soft copper
2. INSULATION: Cross-Linked Polyethylene (XLP) as approved by CSA on Types RW90 XLP -40°C per CSA C22.2,
No. 131, color code: 2/C black, white; 3/C red, black, blue; 4/C red, black, blue, white; more than 4/C numbered
3. GROUNDING CONDUCTOR: 14 AWG uninsulated Class B stranded grounding conductor is included in the cable assembly
4. ASSEMBLY: Multiple conductor cables are assembled with suitable fillers and binder tape
5. INNER JACKET: Polyvinyl Chloride (PVC) heat-, flame- and moisture-resistant jacket, rated -40°C
6. ARMOR: Aluminum or galvanized steel interlocking armor
7. OVERALL JACKET: Polyvinyl chloride (PVC) heat-, flame- and moisture-resistant jacket, rated -40°C, the standard color is black but colored jackets are available on request,
meets Ontario Hydro Spec. L-891 SM-77 flame test and FT4 vertical tray flame test
8. AMPACITY: Based on 90°C column of Table 2 of the 2009 Canadian Electric Code, allowable ampacities for not more than 3 copper conductors in raceway or cable based on
30°C ambient temperature. Ampacity correction factors for number of conductors from Table 5C of the CEC
9. TEMPERATURE: -40°C to 90°C
10.VOLTAGE: 600 V
APPLICATIONS
For exposed or concealed wiring in wet or dry locations. For use in ventilated, non-ventilated and ladder type cable troughs and ventilated flexible cableway in wet or dry
locations. For direct earth burial. Typical applications are for power, lighting and control circuits in: pulp and paper mills, steel mills, food processing plants, commercial
centers, mines, generating stations, refineries, industrial plants and chemical plants.

Note: After catalog number use; «SJ» for steel, «AJ» for aluminum (e.g. 7TF-1003AJ).
Diameters and weights may vary among manufacturers

7TF-1002, 7TF-1003, 7TF-1004, 7TF-1005, 7TF-1006, 7TF-1007, 7TF-1008, 7TF-1009, 7TF-1010, 7TF-1011, 7TF-1012, 7TF-1013, 7TF-1014, 7TF-1015, 7TF-1016, 7TF-1017, 7TF-1018, 7TF-1019, 7TF-1020, 7TF-1025, 7TF-1030, 7TF-1040, 7TF-1050

Armored Cable 600V 10 AWG Multiconductor en: Tijuana, Rosarito, Mexicali, Ensenada, Tecate, San Luis Rio Colorado, Son, La Paz, BCS, Los Cabos BCS, Mexico

Etiquetado con: , , , , , , , , , , , , , , , , , , , , , , , ,
Publicado en: Cable y Alambre, Wire and Cable

Deja una respuesta

Tu dirección de correo electrónico no será publicada. Los campos obligatorios están marcados con *

*

Descarga Aquí este Catálogo
Caddy Erico Mexico, Caddy Nvent Mexico, Erico Mexico, Nvent Mexico,
Subscribase a este sitio