600V Multiconductor Norteck UL CSA

600V Multiconductor Norteck UL CSA

Armored Cable 600V Multiconductor Norteck UL CSA

600V Multiconductor Norteck UL CSA

7XD-1402AJ, 7XD-1404AJ, 7XD-1405AJ, 7XD-1407AJ, 7XD-1409AJ, 7XD-1412AJ, 7XD-1415AJ, 7XD-1419AJ, 7XD-1425AJ, 7XD-1430AJ, 7XD-1437AJ, 7XE-1202AJ, 7XE-1203AJ, 7XE-1204AJ, 7XE-1205AJ, 7XE-1207AJ, 7XE-1209AJ, 7XE-1212AJ, 7XE-1215AJ, 7XE-1219AJ, 7XE-1225AJ, 7XE-1230AJ, 7XE-1237AJ, 7XF-1002AJ, 7XF-1003AJ, 7XF-1004AJ, 7XF-1005AJ, 7XF-1007AJ, 7XF-1009AJ, 7XF-1012AJ

Somos Especialistas en Cables. Distribuimos en toda la Republica Mexicana: Innovative Trade Center, Tel: (664) 621 33 36 / 621 30 09 ventas@innovative.com.mx, soporte@innovative.com.mx, Tijuana, B. C. www.innovative.com.mx

Armored Cable 600V Multiconductor Norteck UL CSA

Aluminio armadura entrelazada
aislamiento XLP
El forro de PVC interior
90 ° C, UL y CSA 600 V
ESPECIFICACIONES DE
1. CONDUCTOR: Clase B trenzado, desnudo, cobre recocido por ASTM B3 y B8
2. Aislamiento: Polietileno reticulado (XLP) por ICEA S-73-532 (NEMA WC57), UL Tipo XHHW-2 y Tipo CSA RW90. El código de colores es el método 1,
Tabla E-2 (anteriormente K-2) (dos y tres conductores) o el método de 4 (cuatro o más conductores)
3. MONTAJE: Los conductores aislados están cableados con un solo cable a tierra sin aislamiento y materiales de relleno para hacer ronda
4. Chaqueta interior: Negro, luz solar resistente al cloruro de polivinilo (PVC) aplicada por ICEA, chaqueta cumple con los requisitos bajos precios del gas ácido de CSA C22.2 No. 0.3
5. Armadura: Aluminio enclavada armadura
6. CHAQUETA EN GENERAL: Negro, luz solar resistente al cloruro de polivinilo (PVC) que se aplica en general por ICEA, chaqueta cumple con los requisitos bajos precios del gas ácido de CSA C22.2 No. 0.3
7. NORMAS: Los cables pasan UL 1685 y IEEE 1202 / T4 libre (70.000 Btu / hr) y ensayos a la llama ICEA T-29-520 (210,000 Btu / hr). Los cables están marcados «para uso CT» y conoce a CSA -40 ° C
impacto fría y ensayo de doblado. Los conductores individuales enumeran Tipo XHHW-2 por UL 44 y CSA tipo RW90. Cable en la lista UL tipo MC según UL 1569 y CSA Tipo Teck 90
por C22.2 No. 131
8. AMPACIDAD: Basado en no más de tres conductores en la pista de rodadura cable o tierra sobre la base de una temperatura ambiente de 30 ° C por 2008, la tabla NEC 310.16 multiconductores valores
han sido reducida por 2008 Tabla NEC 310.15 (B) (2) (a)
9. Temperatura: 90 ° C
10.VOLTAGE: UL y CSA 600 V
APLICACIONES
Para su uso en circuitos de control en plantas industriales, edificios comerciales, y las aplicaciones centrales y subestaciones de servicios públicos. Puede ser instalado en bandejas, bastidores, perchas, etc.,
eliminando la necesidad de conducto. Conveniente para la instalación en interiores y exteriores. Puede utilizarse en NEC Clase I y II, Div 2 localizaciones

Armored Cable 600V Multiconductor Norteck UL CSA

Aluminum interlocked armor
XLP insulation
Inner PVC jacket
90ºC, UL and CSA 600 V
SPECIFICATIONS OF
1. CONDUCTOR: Class B stranded, bare, annealed copper per ASTM B3 and B8
2. INSULATION: Cross-Linked Polyethylene (XLP) per ICEA S-73-532 (NEMA WC57), UL Type XHHW-2 and CSA Type RW90. Color coding is Method 1,
Table E-2 (formerly K-2) (two and three conductors) or Method 4 (four or more conductors)
3. ASSEMBLY: The insulated conductors are cabled with a single uninsulated ground wire and fillers to make round
4. INNER JACKET: Black, sunlight-resistant Polyvinyl Chloride (PVC) applied per ICEA, jacket meets low acid gas requirements of CSA C22.2 No. 0.3
5. ARMOR: Aluminum interlocked armor
6. OVERALL JACKET: Black, sunlight-resistant Polyvinyl Chloride (PVC) applied overall per ICEA, jacket meets low acid gas requirements of CSA C22.2 No. 0.3
7. STANDARDS: Cables pass UL 1685 and IEEE 1202/FT4 (70,000 Btu/hr) and ICEA T-29-520 (210,000 Btu/hr) flame tests. Cables are marked «for CT use» and meet CSA -40°C
cold impact and bend test. Individual conductors listed Type XHHW-2 per UL 44 and CSA Type RW90. Cable listed UL Type MC per UL 1569 and CSA Type Teck 90
per C22.2 No. 131
8. AMPACITY: Based on not more than three conductors in raceway or cable or earth based on an ambient temperature of 30°C per 2008 NEC table 310.16, multiconductor values
have been derated per 2008 NEC Table 310.15(B)(2)(a)
9. TEMPERATURE: 90°C
10.VOLTAGE: UL and CSA 600 V
APPLICATIONS
For use in control circuits in industrial plants, commercial buildings, and central and substation utility applications. May be installed in trays, racks, hangers, etc.,
eliminating the need for conduit. Suitable for indoor and outdoor installation. May be used in NEC Class I and II, Div 2 locations

7XD-1402AJ, 7XD-1404AJ, 7XD-1405AJ, 7XD-1407AJ, 7XD-1409AJ, 7XD-1412AJ, 7XD-1415AJ, 7XD-1419AJ, 7XD-1425AJ, 7XD-1430AJ, 7XD-1437AJ, 7XE-1202AJ, 7XE-1203AJ, 7XE-1204AJ, 7XE-1205AJ, 7XE-1207AJ, 7XE-1209AJ, 7XE-1212AJ, 7XE-1215AJ, 7XE-1219AJ, 7XE-1225AJ, 7XE-1230AJ, 7XE-1237AJ, 7XF-1002AJ, 7XF-1003AJ, 7XF-1004AJ, 7XF-1005AJ, 7XF-1007AJ, 7XF-1009AJ, 7XF-1012AJ

Armored Cable 600V Multiconductor Norteck UL CSA en: Tijuana, Rosarito, Mexicali, Ensenada, Tecate, San Luis Rio Colorado, Son, La Paz, BCS, Los Cabos BCS, Mexico

Etiquetado con: , , , , , , , , , , , , , , , , , , , , , , ,
Publicado en: Cable y Alambre, Wire and Cable

Deja una respuesta

Tu dirección de correo electrónico no será publicada. Los campos obligatorios están marcados con *

*

Descarga Aquí este Catálogo
Subscribase a este sitio