EPR CPE CSPE

EPR CPE CSPE

Power Cable EPR CPE CSPE

EPR CPE CSPE

3DC-0601, 3DC-0401, 3DC-0201, 3DC-1011, 3DC-2021, 3DC-3031, 3DC-4041, 3DC-2501, 3DC-3501, 3DC-5001, 3DC-7501, 3DC-10001

Somos Especialistas en Cables. Distribuimos en toda la Republica Mexicana: Innovative Trade Center, Tel: (664) 621 33 36 / 621 30 09 ventas@innovative.com.mx, soporte@innovative.com.mx, Tijuana, B. C. www.innovative.com.mx

Power Cable EPR CPE CSPE

aislamiento de EPR
CPE o chaqueta CSPE
no apantallado
Listado UL Tipo MV-90
PRESUPUESTO
1. CONDUCTOR: Clase B Trenzado, recocido, cobre desnudo según la norma ASTM B-3 y B-8, escudo cadena es un compuesto semiconductor extruido por ICEA S-96-659 (NEMA WC71)
2. AISLAMIENTO: Caucho de etileno propileno (EPR), que cumple o excede ICEA S-96-659 y UL 1072. Para lugares húmedos o secos por UL 1072 y NEC artículo 328
3. CHAQUETA EN GENERAL: CPE o CSPE
4. NORMAS: Listado Tipo MV-90 por UL 1072 para lugares húmedos y secos. Cumple con los requisitos de ICEA S-96-659 (NEMA WC71). Tamaños 1/0 y mayor luz del sol marcada Resistentes
IEEE pasar la prueba de la llama 383 70.000 Btu / hr y están marcados «para uso TC»
5. AMPACIDAD: Sobre la base de tres cables conductores individuales aislados en el conducto de aire de acuerdo con la Tabla NEC 310.73 con una temperatura del conductor de 90 ° C y una temperatura ambiente de 40 ° C
6. Temperatura: 90 ° C
7. TENSION: 2.400 V
APLICACIONES
Para su uso en circuitos de potencia de hasta 2.400 V en la que los escudos no pueden ser debidamente terminados y donde el espacio es limitado. Cable se utiliza para aplicaciones de energía en plantas químicas,
refinerías, fábricas de acero, plantas industriales, subestaciones y centrales eléctricas. Es ideal para aplicaciones donde se requiere una mayor durabilidad.

Diámetros y pesos pueden variar entre los fabricantes.

Power Cable EPR CPE CSPE

EPR insulation
CPE or CSPE jacket
Nonshielded
UL Listed Type MV-90
SPECIFICATIONS
1. CONDUCTOR: Class B stranded, annealed, bare copper per ASTM B-3 and B-8, strand shield is an extruded semiconducting compound per ICEA S-96-659 (NEMA WC71)
2. INSULATION: Ethylene Propylene Rubber (EPR) which meets or exceeds ICEA S-96-659 and UL 1072. For wet or dry locations per UL 1072 and NEC Article 328
3. OVERALL JACKET: CPE or CSPE
4. STANDARDS: Listed Type MV-90 per UL 1072 for wet and dry locations. Meets requirements of ICEA S-96-659 (NEMA WC71). Sizes 1/0 and larger marked Sunlight Resistant and
pass IEEE 383 70,000 Btu/hr flame test and are marked «for CT use»
5. AMPACITY: Based on three single conductor cables in isolated conduit in air per NEC Table 310.73 with a conductor temperature of 90°C and an ambient temperature of 40°C
6. TEMPERATURE: 90°C
7. VOLTAGE: 2,400 V
APPLICATIONS
For use in power circuits up to 2,400 V where shields cannot be properly terminated and where space is limited. Cable is used for power applications in chemical plants,
refineries, steel mills, industrial plants, utility substations and generating stations. Ideally suited for applications where increased durability is required.

Diameters and weights may vary among manufacturers.

3DC-0601, 3DC-0401, 3DC-0201, 3DC-1011, 3DC-2021, 3DC-3031, 3DC-4041, 3DC-2501, 3DC-3501, 3DC-5001, 3DC-7501, 3DC-10001

Power Cable EPR CPE CSPE en: Tijuana, Rosarito, Mexicali, Ensenada, Tecate, San Luis Rio Colorado, Son, La Paz, BCS, Los Cabos BCS, Mexico

Etiquetado con: , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , ,
Publicado en: Cable y Alambre, Wire and Cable