PVC Nylon PVC

PVC Nylon PVC

Control Cable PVC Nylon PVC

PVC Nylon PVC

1802, 1803, 1804, 1805, 1807, 1810, 1812, 1815, 1819, 1837, 1602, 1603, 1604, 1605, 1606, 1607, 1608, 1609, 1612, 1615, 1619, 1625, 1630, 1637, 1402, 1403, 1404, 1405, 1406, 1407, 1408, 1409, 1410, 1412, 1415, 1419, 1425, 1430, 1437, 1202, 1203, 1204, 1205, 1206, 1207, 1208, 1209, 1212, 1219, 1220, 1225, 1230, 1237, 1002, 1003, 1004, 1005, 1007, 1009, 1012

Somos Especialistas en Cables. Distribuimos en toda la Republica Mexicana: Innovative Trade Center, Tel: (664) 621 33 36 / 621 30 09 ventas@innovative.com.mx, soporte@innovative.com.mx, Tijuana, B. C. www.innovative.com.mx

Control Cable PVC Nylon PVC

aislamiento de PVC-nylon
El forro de PVC
90 ° C, 600 V
ESPECIFICACIONES
1. CONDUCTORES: Clase B Trenzado de cobre desnudo según UL 83 y 62
2. AISLAMIENTO: Policloruro de vinilo (PVC) por UL Tipo 62 para TFFN (18-16 AWG) o UL 83 para el tipo THWN o THHN, espesor nominal es de 15 milésimas de pulgada para los tamaños de 18-12 AWG y 20 milésimas de pulgada
de 10 AWG
3. Envoltura de aislamiento: Cada conductor aislado está encamisado con la reunión de nylon UL 62 para el tipo THHN o UL 83 para el tipo THWN o THHN, espesor mínimo es de 4 milésimas de pulgada
4. CÓDIGO DE COLORES: ICEA Método 1, Tabla E-2 (anteriormente K-2)
5. Montaje: Los conductores están cableados con cargas cuando sea necesario para hacer todo el año, dos cables conductores son planas
6. CHAQUETA EN GENERAL: La luz solar resistente al cloruro de polivinilo (PVC) por UL 1277
7. NORMAS: cumple con UL 1277 Requisitos para los cables que tienen conductores P tipo THWN o THHN (THWN), los cables se enumeran para el entierro directo y cumplen con la norma IEEE 1202, IEEE 383 y
UL 1685 Btu / hr ensayos a la llama. Tres conductores y grandes construcciones cumplen UL 1277 requisitos para tiradas a la vista y son clasificados Tipo TC-ER (bandeja de cables, ejecuta expuesta)
8. AMPACIDAD: Basado en no más de tres conductores en la pista de rodadura cable o tierra con una temperatura ambiente de 30ºC según la Tabla NEC 310.16, los valores se han reducido su potencia
donde corresponda
9. Temperatura: 90 ° C
10.VOLTAGE: 600 V
APLICACIONES
Diseñado por el poder y el control, telemetría, control de relé, el control del tráfico, la distribución, la iluminación y la transmisión de la señal. Puede utilizarse en Clase I, Div. 2 y Clase II, Div. 2
Lugares peligrosos por NEC Art. 501 y 502. Estos cables también cumplen con el art. «Bandejas de cable» 392 y 336 Arte «bandeja de cables de potencia y control.»

Control Cable PVC Nylon PVC

PVC-nylon insulation
PVC jacket
90°C, 600 V
SPECIFICATIONS
1. CONDUCTORS: Class B stranded bare copper per UL 83 and 62
2. INSULATION: Polyvinyl Chloride (PVC) per UL 62 for Type TFFN (18-16 AWG) or UL 83 for Type THWN or THHN wire, nominal thickness is 15 mils for sizes 18-12 AWG and 20 mils
for 10 AWG
3. INSULATION JACKET: Each insulated conductor is jacketed with nylon meeting UL 62 for Type THHN or UL 83 for Type THWN or THHN wire, minimum thickness is 4 mils
4. COLOR CODE: ICEA Method 1, Table E-2 (formerly K-2)
5. ASSEMBLY: Conductors are cabled with fillers where necessary to make round, two conductor cables are flat
6. OVERALL JACKET: Sunlight-resistant Polyvinyl Chloride (PVC) per UL 1277
7. STANDARDS: Meets UL 1277 requirements for Type TC cables having THWN or THHN (THWN) conductors, cables are listed for direct burial and meet the IEEE 1202, IEEE 383 and
UL 1685 Btu/hr flame tests. Three conductor and larger constructions meet UL 1277 requirements for Exposed Runs and are rated Type TC-ER (Tray Cable, Exposed Runs)
8. AMPACITY: Based on not more than three conductors in raceway or cable or earth with an ambient temperature of 30ºC per NEC Table 310.16, the values have been derated
where applicable
9. TEMPERATURE: 90ºC
10.VOLTAGE: 600 V
APPLICATIONS
Designed for power and control, telemetering, relay control, traffic control, switching, lighting and signal transmission. May be used in Class I, Div. 2 and Class II, Div. 2
Hazardous Locations per NEC Art. 501 and 502. These cables also conform to Art. 392 «Cable Trays» and Art 336 «Power and Control Tray Cable.»

2A-1802, 2A-1803, 2A-1804, 2A-1805, 2A-1807, 2A-1810, 2A-1812, 2A-1815, 2A-1819, 2A-1837, 2A-1602, 2A-1603, 2A-1604, 2A-1605, 2A-1606, 2A-1607, 2A-1608, 2A-1609, 2A-1612, 2A-1615, 2A-1619, 2A-1625, 2A-1630, 2A-1637, 2A-1402, 2A-1403, 2A-1404, 2A-1405, 2A-1406, 2A-1407, 2A-1408, 2A-1409, 2A-1410, 2A-1412, 2A-1415, 2A-1419, 2A-1425, 2A-1430, 2A-1437, 2A-1202, 2A-1203, 2A-1204, 2A-1205, 2A-1206, 2A-1207, 2A-1208, 2A-1209, 2A-1212, 2A-1219, 2A-1220, 2A-1225,2A-1230, 2A-1237, 2A-1002, 2A-1003, 2A-1004, 2A-1005, 2A-1007, 2A-1009, 2A-1012

PVC Nylon PVC en: Tijuana, Rosarito, Mexicali, Ensenada, Tecate, San Luis Rio Colorado, Son, La Paz, BCS, Los Cabos BCS

Etiquetado con: , , , , , , , , , , , , , , , , , , , , , , , ,
Publicado en: Cable y Alambre, Wire and Cable